Threshold gas detectors DG/A

DG/A two-threshold detectors are designed to detect the presence of dangerous concentrations of explosive or toxic gases or vapors in the air in industrial, enclosed spaces. They feature a replaceable sensor module with two alarm thresholds (thresholds set at the production stage, with a built-in third threshold that is usually the upper recommended measurement range).

DG/A detectors have a passive 4-20 mA, 3-wire interface and are designed to work with MDP alarm modules or other control modules that accept devices with a passive (current-absorbing) output.

DG/A detectors are of standard design and cannot be used in areas classified as hazardous due to the presence of gases, vapors, or dust.

Features

  • replaceable, intelligent semiconductor gas sensor;
  • two alarm thresholds set at the production stage (the third threshold is usually the upper measurement range of the gas sensor, signaled only optically), 4-20 mA passive, 3-wire interface;
  • built-in event history (analysis available from the manufacturer), indication of the recommended calibration period; built-in test procedure to recognize output cables (after power-up);
  • thermal compensation system (can be used in variable environmental conditions);
  • easy gas penetration through the sensor cover = relatively short detector response time;
  • built-in optical signaling (multi-color LED);
  • removable terminals with the possibility of mounting single and multi-wire cores (cable - without crimping sleeves);
  • splash-proof IP44 gas sensor cover (in the recommended mounting position);
  • can be equipped with a mechanical cover made of AR-1 profiled pipes (installation in areas exposed to mechanical damage, e.g., warehouses, wholesale stores, parking lots);
  • can be equipped with a housing for installation on a ventilation duct (version DG/w);
  • all detectors are calibrated in our own GAZEX Calibration Laboratory operating in accordance with the PN-EN ISO/IEC 17025 standard (PCA accreditation no. AP150).

Offered models

Model Gas sensor module Sensor Substance/property Standard alarm thresholds or measuring range Supply voltage Net price C.g.
New MS-12/N Semiconductor Methane (CH4)
10/30/(40)
%LEL
System powered PLN769.00 N
New MS-14/N Semiconductor Methane (CH4)
10/30/(40)
%LEL
System powered PLN769.00 N
New MS-15/N Semiconductor Liquefied petroleum gas (LPG)
10/30/(40)
%LEL
System powered PLN769.00 N
New MS-22/NL Semiconductor Carbon monoxide (CO)
(TWA/STEL) 20/100/(300)
ppm
System powered F
New MS-31/N Semiconductor Organic compounds
20/40/(50)
%LEL
System powered F
New MS-41/N Semiconductor Ammonia (NH3)
500/1500/(2000)
ppm
System powered F
New MS-61/N Semiconductor Refrigerant R32
or Refrigerant R410A
1000/2000/(2500)
ppm
System powered F
New MS-71/N Semiconductor Acetylene (C2H2)
or Hydrogen (H2)
10/30/(40)
%LEL
System powered F
New MS-73/N Semiconductor Hydrogen (H2)
10/30/(40)
%LEL
System powered F
Model Gas sensor module Sensor Substance/property Standard alarm thresholds or measuring range Supply voltage Contact control outputs Voltage control outputs 12VDC Two-state outputs (threshold) Control output "Fault" Output controlling the shut-off valve Output in 4-20mA standard Output in 0-10V standard Output in 2-10V standard Output in RS-485 standard Visual signalling, built-in Acoustic signaling, built-in Internal battery Dimensions Net price C.g.
New MS-12/N Semiconductor Methane (CH4)
10/30/(40)
%LEL
System powered 2 110 x 153 x 60 mm PLN769.00 N
New MS-14/N Semiconductor Methane (CH4)
10/30/(40)
%LEL
System powered 2 110 x 153 x 60 mm PLN769.00 N
New MS-15/N Semiconductor Liquefied petroleum gas (LPG)
10/30/(40)
%LEL
System powered 2 110 x 153 x 60 mm PLN769.00 N
New MS-22/NL Semiconductor Carbon monoxide (CO)
(TWA/STEL) 20/100/(300)
ppm
System powered 2 110 x 153 x 60 mm F
New MS-31/N Semiconductor Organic compounds
20/40/(50)
%LEL
System powered 2 110 x 153 x 60 mm F
New MS-41/N Semiconductor Ammonia (NH3)
500/1500/(2000)
ppm
System powered 2 110 x 153 x 60 mm F
New MS-61/N Semiconductor Refrigerant R32
or Refrigerant R410A
1000/2000/(2500)
ppm
System powered 2 110 x 153 x 60 mm F
New MS-71/N Semiconductor Acetylene (C2H2)
or Hydrogen (H2)
10/30/(40)
%LEL
System powered 2 110 x 153 x 60 mm F
New MS-73/N Semiconductor Hydrogen (H2)
10/30/(40)
%LEL
System powered 2 110 x 153 x 60 mm F

Suggested products

Splash-proof enclosures AP-1
Splash-proof enclosures to protect detectors from adverse weather conditions and mechanical damage
Tubular shields AR-1
Profiled tube guards to protect the detector from direct mechanical damage
Gas test sets GTS
Test sets for verifying the correct operation of detectors by injecting a gaseous test mixture into the measuring chamber of the detector