DG-P0E.CL2/MR
                    
                        
                        
                        
                        
                        
                        
                        
                    
                
            Type of device: DG-P/MR Description of device type
Digital DG-P/MR detectors are designed for continuous monitoring of gases indoors. The detector performs cyclic measurements of the gas concentration in ambient air . When preset concentration values are exceeded (for a threshold version), the detector’s optical alarm signaling is activated, the built-in relays change their status and the information is transferred to a digital control module (for the measurement version the concentration value) - using a network in the industrial standard RS-485. The detectors are designed for operation in the Digital Gas Detection System.
The detectors have an exchangeable module with a semiconductor, electrochemical or optical sensor (Infra-Red). The interchangeability of the sensory modules improves maintenance, simplifies calibration and reduces operating costs.
The DG-P/MR detectors are of standard design and cannot be used in areas classified as explosive atmospheres of gases, vapours or dust.
Area of application
- industrial plants, logistics centres, public facilities;
 - extensive rooms at risk of toxic or explosive gas emissions with locally controlled sirens.
 
Features
- communication, control and transmission of information through the port in RS-485 standard, with MODBUS RTU protocol;
 - two alarm thresholds or measurement mode (for electrochemical sensors and Infra-Red);
 - two built-in relays with NO/NC contact, on a removable board (for A1 and A2 state, possibility of threshold adjustment in the measurement mode);
 - sensor in an interchangeable intelligent module (interchangeable with DG/F and DG/P type detectors);
 - sensor can be selected for the application;
 - short detector response time;
 - built-in control microprocessor means reliable and stable operation;
 - thermal compensation system;
 - history of alarm states;
 - semi-automatic addressing in digital network (without opening the housing);
 - removable, screwless terminals with possibility of connecting two FTP wires;
 - selective LED optical optimization;
 - two cable entries – easy connection of successive detectors (loop-through);
 - optionally, the possibility of being equipped with an additional casing made of steel pipes (AR-1d) or a casing for ventilation ducts (DG/w version);
 - configuration of detector settings via dedicated software „DETnet View”, available at https://www.gazex.pl/en/software/;
 - all detectors are calibrated in our own GAZEX Calibration Laboratory operating in accordance with PN-EN ISO/IEC 17025 (PCA accreditation no. AP150).
 
Device model: DG-P0E.CL2/MR
Technical parameters
- Contact control outputs
 - 2
 - Output in RS-485 standard
 - ✓
 - Visual signalling, built-in
 - ✓
 - Supply voltage
 - 24 V DC
 - Dimensions
 - 110 x 140 x 55 mm
 - EAN Code
 - 5901769656185
 - Net price
 - PLN1,449.00 N
 
| Gas sensor module | Sensor | Substance/property | Standard alarm thresholds or measuring range | |
|---|---|---|---|---|
| MS-P0E.CL2/N | Electrochemical | 
                    
                    Chlorine (Cl2) | 
                 0 ÷ 10 | 
                ppm | 
            
Documentation
| Series | Technical data | User Manual | Declaration of conformity | |
|---|---|---|---|---|
| W6 | Download file | — | — | |
| Archived series | ||||
| W5 | Download file | — | Download file | |
| W4 | Download file | — | Download file | |
| W3 | Download file | — | Download file | |