![DG-0E.COCL2/M](/media/cache/fb/8a/fb8af8f35afe15a1241a2498b0e1afda.png)
DG-0E.COCL2/M
Product model withdrawn from sale
Device group: Threshold gas detectorsDevice type: DG/M Description of device type
Digital detector type DG/M is designed for continuous monitoring of the concentration of specified gas on the premises monitored by Digital Gas Detection System. When the concentration exceeds a preset threshold, the detector produces a signal in the system via RS-485 network and switches on built-in LEDs.
Detector can be equipped with a semiconductor, electrochemical or Infra-Red sensor.
The detector has a removable module with the intelligent sensor, which facilitates maintenance and lowers operating costs. Detector DG/M cannot be used in hazardous locations.
Scope of application
- industrial areas, factories, logistics centers, public buildings
- dispersed gas detection systems
Features
- communication, control and transfer of information through the port RS-485 with MODBUS RTU protocol;
- short response time;
- gas sensor in intelligent, EXCHANGEABLE module;
- built-in microprocessor control provides reliability, stability, thermal compensation system, the history of alarm, semi-automatic address control;
- 3 or 2 alarm thresholds mode or gas concentration measurement mode;
- optical signaling (4x LEDs); fast removable connection pins for FTP type cables;
- splash-proof case (IP44)
- 2 cable glands enabling easy connection of multiple detectors in series;
- optional: additional steel pipes cover (AR-1d) or the duct-mouting casing (version DG…/Mw);
- all detectors are calibrated in our own GAZEX Calibration Laboratory operating in accordance with PN-EN ISO/IEC 17025 (PCA accreditation No AP150).
Device model: DG-0E.COCL2/M
Technical parameters
- Output in RS-485 standard
- Visual signalling, built-in
- Supply voltage
- 24VDC
- Dimensions
- 110 x 140 x 55 mm
Gas sensor module | Sensor | Substance/property | Standard alarm thresholds or measuring range | |
---|---|---|---|---|
MS-0E.COCL2/N | Electrochemical |
Phosgene (COCl2) |
0,2/0,4 |
ppm |
Documentation
Series | Technical data | Device information sheet | User Manual | Declaration of conformity |
---|---|---|---|---|
W6 | — | — | — | — |
Archived series | ||||
W5 | — | — | — | — |
W4 | — | — | — | — |
W3 | — | — | — | — |
Suggested products
![](/media/cache/90/7d/907d222d71203bdabae4860a2f45228a.png)
Splash-proof enclosures AP-1
Splash-proof enclosures to protect detectors from adverse weather conditions and mechanical damage
![](/media/cache/47/25/472550a0e6552a99adb6e8a5f8b539d8.png)
Tubular shields AR-1
Profiled tube guards to protect the detector from direct mechanical damage
![](/media/cache/69/dd/69ddc24a31bb9c605e9d91b548139830.png)
DG/w
Adaptation of DG/F, DG/M, DG/P or DG/PV detectors for installation into a ventilation duct
![](/media/cache/b1/b9/b1b970bcda4334ec8fe55fc122579773.png)
MR2
Modules extending functionality of DG/M and DG-P/M detectors with two NO/NC relays
![](/media/cache/c8/a9/c8a9d39d5bea3f402e86d2d75ad5aa21.png)
Gas test sets GTS
Test sets for verifying the correct operation of detectors by injecting a gaseous test mixture into the measuring chamber of the detector